This setpoint is used to adjust time period the relative load level must be above
the Ld shed level limit to close the next load shedding output.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
Setpoint: Ld recon level
This setpoint is used to adjust the relative load level (in % of nominal power of
gen-set) for load reconnection. When the relative load level drops below this level
for more than Ld recon delay time the next load can be reconnected back.
The appropriate load shedding output is either opened automatically when the
condition above is fulfiled (AutoLd recon = ENABLED) or manually by activation of
the input ManualLdRecon.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
Setpoint: Ld recon del
This setpoint is used to adjust time period the relative load level must be below
the Ld recon level limit to allow reconnection of next load group.
NOTE:
Learn more about load shedding in the separate chapter Load shedding.
Setpoint: AutoLd recon
This setpoint selects whether the reconnection of the load occurs automatically
when the relative load level stays below the reconnection limit for a period of the
reconnection delay or the reconnection must be initiated manually by the input