IGS-NT Combi, SW Version 3.0, ©ComAp May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
358
Description
This output is closed while the Fuel theft alarm is present in the alarm list. This
alarm occurs when the fuel level value measured at the analog input Fuel level
drops faster than is the limit adjusted by setpoint MaxFuelDrop.
Alarm output: PLC State 1
Related FW
3.0
Description
The output is closed while the alarm generated by the PLC block Force prot 1 is
present in the alarm list.
NOTE:
The actual text, which appears in the alarm list, can be changed in GenConfig.
Alarm output: PLC State 2
Related FW
3.0
Description
The output is closed while the alarm generated by the PLC block Force prot 2 is
present in the alarm list.
NOTE:
The actual text, which appears in the alarm list, can be changed in GenConfig.
Alarm output: PLC State 3
Related FW
3.0
Description
The output is closed while the alarm generated by the PLC block Force prot 3 is
present in the alarm list.
NOTE:
The actual text, which appears in the alarm list, can be changed in GenConfig.
Alarm output: PLC State 4
Related FW
3.0
Description
The output is closed while the alarm generated by the PLC block Force prot 4 is
present in the alarm list.
NOTE:
The actual text, which appears in the alarm list, can be changed in GenConfig.
Alarm output: UnivState 1
Related
FW
3.0
Description
The output is closed while the alarm generated by the Universal analog protection, where
the Message #1 is used, is present in the alarm list.
NOTE:
The actual text of the message depends on configuration.