IGS-NT Combi, SW Version 3.0, ©ComAp May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
146
Force value
possible
YES
Description
The setpoint is used to switch on and off the output Bin selector 1.
Setpoint: Bin selector 2
Group
Engine params
Range [units]
OFF, ON [-]
Related FW
3.0
Force value
possible
YES
Description
The setpoint is used to switch on and off the output Bin selector 2.
Setpoint: Bin selector 3
Group
Engine params
Range [units]
OFF, ON [-]
Related FW
3.0
Force value
possible
YES
Description
The setpoint is used to switch on and off the output Bin selector 3.
Setpoint: Bin selector 4
Group
Engine params
Range [units]
OFF, ON [-]
Related FW
3.0
Force value
possible
YES
Description
The setpoint is used to switch on and off the output Bin selector 4.
Setpoint: MaxFuelDrop
Group
Engine params
Range [units]
3 .. 50 [%/h]
Related FW
3.0
Description
This setpoint adjusts the maximal allowed drop of the fuel level within one hour. If
measured drop is higher then Fuel theft alarm is issued. The setpoint should be
adjusted according to the maximal hour fuel rate of the engine and capacity of the
tank.
NOTE:
The logical analog input Fuel level must be configured onto the physical analog
input where fuel level sensor is connected.