Reset Actual Alarms selection
It is possible to determine the behavior of alarms that are in alarm list when Fault Reset button is pressed.
Select behavior with ComProtSetting:ResetActAlarms.
Pressing of the fault reset button (at any terminal or external button) resets
only inactive alarms. Active alarms remain in the alarmlist unchanged and must be reset
again when they become inactive.
Pressing of the fault reset button (at any terminal or external button) resets all alarms that
are currently present in the alarm list. Inactive alarms disappear from the alarm list
immediately, active alarms are changed to "confirmed" state and disappear when the
alarm condition disappear or the alarm starts to be blocked.
NOTE:
ENABLED position corresponds to the method how the IG-classic and IS-classic controllers handled the
alarms.