11
Alarm AL1 type
01
Range: 00 to 19 (See Appendix 4.2. Alarm type and function)
↓ SET
ALt1
Delay of alarm AL1 activation in profile control mode
0
Range: 0 to 99.59 min
↓ SET
0 = flicker alarm, 99.59 = continued, other values = on-delay time
ALd2
Alarm AL2 type
01
Range: 00 to 19
↓ SET
ALt2
Delay of alarm AL2 activation in profile control mode
0
Range: 0 to 99.59 min
↓ SET
0 = flicker alarm, 99.59 = continued, other values = on-delay time
ALd3
Alarm AL3 type
01
Range: 00 to 19
↓ SET
ALt3
Delay of alarm AL3 activation in profile control mode
0
Range: 0 to 99.59 min
↓ SET
0 = flicker alarm, 99.59 = continued, other values = on-delay time
HYSA
Alarm hysteresis
0
Range: 0 to 1000
↓ SET
CL01
Calibration of the low limit of the main control output (in case of analog output)
150
Range: LSPL to USPL
↓ SET
See Appendix 4.5. Analog output adjustment
CH01
Calibration of the high limit of the main control output (in case of analog output)
3500
Range: 0 to 9999
↓ SET
See Appendix 4.5. Analog output adjustment