EasyManuals Logo

Comfortmaker F80CTL User Manual

Default Icon
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #47 background imageLoading...
Page #47 background image
F80CTL & G80CTL: Installation, Start–Up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
47
A190159
Fig. 54 – Troubleshooting Guide
1 + 2 BLOWER ON AFTER POWER UP –
(115V OR 24V) – Normal operation.
Blower runs for 90 seconds, if unit is
powered up during a call for heat (R-
W/W1 closed) or when (R-W/W1 opens)
during the blower on-delay period.
6 + 1 IGNITION LOCKOUT – System
failed to ignite gas and prove
flame in 4 attempts. Control will
auto-reset after 3 hours. Refer to
status code #6.
5 ABNORMAL FLAME-PROVING SIGNAL
Flame is proved while gas valve is de-
energized. Inducer will run until fault is
cleared. Check for:
- Stuck open or leaky gas valve.
2 PRESSURE SWITCH DID NOT OPEN –
Check for:
- Obstructed pressure tube.
- Pressure switch stuck closed.
3 LOW-HEAT PRESSURE SWITCH DID
NOT CLOSE OR REOPENED – If opens
during blower on-delay period, blower will
come on for the selected blower off-delay.
If open longer than 5 minutes inducer
shuts off for 15 minutes before retry.
Check for:
- Proper vent sizing.
- Low inlet gas pressure (if LGPS used).
- Inadequate combustion air supply.
- Disconnected or obstructed pressure
tubing.
- Defective or miswired pressure switches
- Excessive wind.
- Restricted vent.
- Defective Inducer motor.
- Low inducer volta
g
e
(
115 VAC
)
4 LIMIT CIRCUIT FAULT – Indicates the
limit, draft safeguard, flame rollout, or
blocked vent switch (if used) is open or the
furnace is operating in high-heat only
mode due to 2 successive low-heat limit
trips. Blower will run for 4 min. or until
open switch remakes whichever is longer.
If open longer than 3 min., code changes
to lockout #7. If open less than 3 min.
status code #4 continues to flash until
blower shuts off. Flame rollout and
blocked vent switch require manual reset.
Check for:
- Restricted vent.
- Loose blower wheel.
- Defective switch or connections.
- Proper vent sizing.
- Dirty filter or restricted duct system.
- Excessive wind.
- Inadequate combustion air supply.
(Flame rollout switch open)
- Blower motor not operating
To determine whether the problem is in the gas
valve, igniter, or flame sensor the system can be
operated in component test mode. To check the
igniter remove the R thermostat connection from
the control, reset power, and put setup switch
SW1-6 in the ON position to start the
component test. Does the igniter glow
orange/white by the end of the 15 second warm-
up period?
Unplug igniter harness from control and
repeat component test by turning setup
switch SW1-6 OFF and then back ON.
Check for 115V between pin 3 and
NEUTRAL-L2 on the control. Was 115V
present for the 15 second period?
Check connections and retry.
If current is near typical value
(4.0-6.0 nominal) and burners
will not stay on, repeat check
in high-heat. If burners will
still not stay on replace
control. If burners operate in
high-heat then switch to low-
heat, check manifold
pressure. If OK, check
burner carryover and flame
sensor location.
Clean flame sensor with fine steel wool
and recheck current. Nominal current is
4.0 to 6.0 microamps.
Is current near typical value?
Replace flame sensor.
Will main burners ignite and stay on? Replace furnace control.
Fixed.
NO
YES
YES
YES
NO
NO
Replace furnace control.
Check for continuity in the
harness and igniter. Replace
defective component.
Reconnect the R thermostat lead and set
thermostat to call for heat. Connect
voltmeter across gas valve connections.
Does gas valve receive 24V?
Does gas valve open and allow gas to
flow?
Do the main burners ignite?
Do the main burners stay on?
Allow blower to come on and
repeat test to check for
intermittent operation.
Check that all gas valves are
turned on. Replace valve.
Check connections. If OK,
replace control.
Check for:
- Inadequate flame carryover
or rough ignition.
- Low inlet gas pressure.
- Proper firing rate.
Repeat call for heat and check flame
sensor current during trial for ignition
period. Is the DC microamps below 0.5?
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
6 IGNITION PROVING FAILURE – If flame is
not sensed during the trial for ignition
period, the control will repeat the ignition
sequence 3 more times before lockout #6 +
1 occurs. If flame signal is lost during the
blower on-delay period, blower will come on
for the selected blower off-delay. Check
the following before going to the next step.
- Gas valve turned off.
- Manual shut-off valve.
- Green/Yellow wire MUST be connected
to furnace sheet metal.
- Flame sensor must not be grounded.
9 HIGH-HEAT PRESSURE SWITCH OR
RELAY DID NOT CLOSE OR REOPENED
Check for:
- Control relay may be defective. - Gas
valve is miswired.
- Refer to status code #3.
10 POLARITY Check for correct line voltage
polarity. If units are twinned, check for
proper low-voltage (24V) transformer
phasing.
7 LIMIT CIRCUIT LOCKOUT – Lockout
occurs if the limit, draft safeguard, flame
rollout, or blocked vent switch (if used) is
open longer than 3 minutes or 10
successive limit trips occurred during high-
heat. Control will auto-reset after 3 hours.
Refer to status code #4.
8 GAS HEATING LOCKOUT – Control will
NOT auto reset. Turn off power and wait
5 minutes to retry. Check for:
- Stuck closed gas valve relay on control.
- Miswire or short to gas valve wire.
2 + 5 INVALID MODEL SELECTION OR SETUP
ERROR – If status code 2 + 5 only flashes 4
times on power-up the control is missing its
model plug PL4 and is defaulting to the
model selection stored in memory. If status
code 2 + 5 flashes continuously it could
indicate any of the following:
- Model plug PL4 is missing and there is no
valid model stored in permanent memory.
This will happen if you forget to install the
model plug PL4 on a service replacement
control.
- Thermostat call with SW1-1 ON.
- Thermostat call with SW1-6 ON.
- SW1-1 and SW1-6 both ON.
- Two different furnace models twinned.
- If replacing a control, be sure to use
correct version (V##) located on control
board) Models supported should be listed
NOTE:
NUMBER IN UPPER LEFT HAND
CORNER REPRESENTS FLASH CODE
4 + 1 BLOWER MOTOR FAULT –
indicates blower failed to reach 250 RPM
or the blower failed to communicate
within the prescribed time limits. 30
seconds after being turned ON or 10
seconds during steady-safe operation.
1 + 5 BLOWER MOTOR LOCKOUT – Indicates
the blower failed to reach 250 RPM or the
blower failed to communicate within 30 seconds
after being turned ON in 2 successive heating
cycles. Control will auto reset after 3 hours.
Refer to status code 4+1.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Comfortmaker F80CTL and is the answer not in the manual?

Comfortmaker F80CTL Specifications

General IconGeneral
BrandComfortmaker
ModelF80CTL
CategoryFurnace
LanguageEnglish