17
3.6 Calibrating the thermometer of the thermostat
There is a possibility to calibrate the thermometer of the thermostat
(to correct the measured temperature). In order to do this, rst press
the “SET” button to go to the main screen. Then press the “DAY
and “HOLD” buttons one after the other. After this, the notice
appears in place of the time characters, and the correction value
appears in place of the measured temperature ( °C by default).
Following this, set the desired correction value using the large
and buttons between -3.0°C and +3.0°C, in 0.1°C increments.
Finally, conrm the setting by pressing the SET” button (if no buttons
are pressed for at least 15 seconds, the setting is automatically
conrmed). After this conrmation, the device goes back to the main
screen. The correction of the measured temperature takes effect a
couple of seconds after the conrmation.