EasyManua.ls Logo

Condec UMC 600IS - Serial Port Configuration

Condec UMC 600IS
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16 UMC 600IS Installation Manual
3.2 Serial Port Configuration
Serial Port 1 is an ASCII-compatible, 20 mA current loop output that is compatable with most printers,
scoreboards, and other remote devices. (Port 2 is not available). Port 1 output can be disabled, set for demand
mode, or set to continuous output data and is optically isolated through the intrinsically safe I/O barrier.
Table 3-7 shows the configuration selections for Parameter 14, which controls the configuration of Port 1. There
is no external access to Port 2 and it should therefore be disabled (Parameter 14.5 set to OFF).
NOTE
: RS232 communication is not available from the UMC 600IS. If RS232 is required, it is recommended that the
Analog Option P/N 19578 be ordered and have U14, C6, C7, C8 and C9 installed.
All serial characters in the data format are in ASCII and consist of the following default settings:
Parameter Subparameter Interpretation
14. oFF Serial communications disabled
14. S1 Port 1: simplex
14. dU Port 1: duplex
14.1 Demand print configuration in net mode
14.1Gtn Three-line output G-N-T
14.1nEt Single line, net print
14.2 Delay after carriage return (CR) enabled
14.2 oFF No delay after CR
14.2 1 1 second delay after CR
14.2 2 2 second delay after CR
14.2 3 3 second delay after CR
14.2 4 4 second delay after CR
14.3 Port 1 configuration
14.3 oFF Port 1 disabled
14.3 dE Demand output
14.3 Co Continuous output
14.4 Port 1 baud rate
14.4 3 300 bps
14.4 6 600 bps
14.4 12 1200 bps
14.4 24 2400 bps
14.4 48 4800 bps
14.4 96 9600 bps
14.5 Port 2 configuration
14.5 oFF Port 2 disabled
Table 3-7. Parameter 14 Configuration Prompts
Data Formats
1 Start bit
7 Data bits
1 Parity bit (odd parity)
1 Stop bit
Table 3-8. Data Formats

Table of Contents