26 Commander SK Getting Started Guide
www.controltechniques.com Issue Number: 1
Safety
Information
Rating
Data
Mechanical
Installation
Electrical
Installation
Keypad and
Display
Parameters
Quick Start
Commissioning
Diagnostics Options
Parameter
List
UL Listing
Information
Defines the jog speed
Determines the input on terminal T2
0-20: Current input 0 to 20mA (20mA full scale)
20-0: Current input 20 to 0mA (0mA full scale)
4-20: Current input 4 to 20mA with current loop loss (cL) trip (20mA full scale)
20-4: Current input 20 to 4mA with current loop loss (cL) trip (4mA full scale)
4-.20:Current input 4 to 20mA with no current loop loss (cL) trip (20mA full scale)
20-.4:Current input 20 to 4mA with no current loop loss (cL) trip (4mA full scale)
VoLt: 0 to 10V input
OFF:Direction of rotation controlled by run forward and run reverse terminals
On:Direction of rotation controlled by preset speed values (use run forward terminal)
Defines preset speeds 1 to 4.
Ld: Active current as a % of motor rated active current
A: Drive output current per phase in A
Fr: Drive output frequency in Hz
SP: Motor speed in rpm
Cd: Machine speed in customer defined units (See Pr 24).
Multiplying factor on motor speed (rpm) to give customer defined units.
No Function Range Defaults Type
13
Not used
14
No Function Range Defaults Type
15 Jog reference 0 to 400.0 Hz 1.5 RW
No Function Range Defaults Type
16 Analog 1 input mode
0-20, 20-0, 4-20, 20-4,
4-.20, 20-.4, VoLt
4-.20 RW
In the 4-20 or 20-4mA modes (with current loop loss) the drive will trip on cL1 if the input
reference is below 3mA. Also, if the drive trips on cL1, the voltage analog input cannot
be selected.
NOTE
No Function Range Defaults Type
17 Enable negative preset speeds OFF (0) or On (1) OFF (0) RW
No Function Range Defaults Type
18 Preset speed 1
±1500 Hz
(Limited by setting of Pr 02
Maximum set speed)
0RW
19 Preset speed 2
20 Preset speed 3
21 Preset speed 4
No Function Range Defaults Type
22 Load display units Ld, A Ld RW
No Function Range Defaults Type
23 Speed display units Fr, SP, Cd Fr RW
No Function Range Defaults Type
24 Customer defined scaling 0 to 9.999 1.000 RW

Other manuals for Control Techniques Commander SK

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Control Techniques Commander SK and is the answer not in the manual?

Control Techniques Commander SK Specifications

General IconGeneral
BrandControl Techniques
ModelCommander SK
CategoryInverter
LanguageEnglish

Related product manuals