48 Commander SK Size 2 to 6 Getting Started Guide
www.controltechniques.com Issue Number: 2
The drive default setting is Ur I mode which means that the drive will carry out an autotune every time the drive is powered-up and enabled. If the load
is not going to be stationary when the drive is powered-up and enabled, then one of the other modes should be selected. Not selecting another mode
could result in poor motor performance or OI.AC, It.AC or OV trips.
Determines the boost level when Pr 41 is set to Fd or SrE.
2.4: 2400 baud
4.8: 4800 baud
9.6: 9600 baud
19.2: 19200 baud
38.4: 38400 baud
Defines the unique address for the drive for the serial interface.
Indicates the version of software fitted to the drive.
Pr 46 to Pr 51 appear when Pr 12 is set to control a motor brake
Defines the brake release and brake apply current thresholds as a % of motor current.
If the frequency is >Pr 48 and the current is >Pr 46, the brake release sequence is started.
If the current is <Pr 47, the brake is applied immediately.
Defines the brake release and brake apply frequencies.
If the current is >Pr 46 and the frequency is > Pr 48, the brake release sequence is started.
If the frequency is <Pr 49 and the drive has been commanded to stop, the brake is applied immediately.
Defines the time between the frequency and load condition being met and the break being released. The ramp is held during this time.
Defines the time between the brake being released and the ramp hold being released.
No Function Range Defaults Type
42 Low frequency voltage boost 0.0 to 50.0 % 3.0 RW
No Function Range Defaults Type
43 Serial communications baud rate 2.4, 4.8, 9.6, 19.2, 38.4 19.2 RW
No Function Range Defaults Type
44 Serial comms address 0 to 247 1 RW
No Function Range Defaults Type
45 Software version 1.00 to 99.99 RO
No Function Range Defaults Type
46 Brake release current threshold
0 to 200 %
50
RW
47 Brake apply current threshold 10
No Function Range Defaults Type
48 Brake release frequency
0.0 to 20.0 Hz
1.0
RW
49 Brake apply frequency 2.0
No Function Range Defaults Type
50 Pre-brake release delay 0.0 to 25.0 s 1.0 RW
No Function Range Defaults Type
51 Post brake release delay 0.0 to 25.0 s 1.0 RW
NOTENOTE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Control Techniques Commander SK3403 and is the answer not in the manual?

Control Techniques Commander SK3403 Specifications

General IconGeneral
BrandControl Techniques
ModelCommander SK3403
CategoryController
LanguageEnglish

Related product manuals