19
Service
wheel
LED
W2 / W3
W4 W5 W6 W7 W8
Full scale
1000
Full scale
4000
Full scale
10000
Full scale
100
Voltage
[V]
[ppm] [ppm] [ppm] [ppm] [--] [m] [--] [--] [--]
6 6000 60 60 9600 8E1
6.1 6100 61
6.2 6200 62
6.3 6300 63
6.4 6400 64
6.5 6500 65 65
6.6 6600 66
6.7 6700 67
6.8 6800 68
6.9 6900 69
7 7000 70 70 19200 8E1
7.1 7100 71
7.2 7200 72
7.3 7300 73
7.4 7400 74
7.5 7500 75 75
7.6 7600 76
7.7 7700 77
7.8 7800 78
7.9 7900 79
8 8000 80 80 2-10 V W=0 A=1 9600 8O1
8.1 8100 81
8.2 8200 82
8.3 8300 83
8.4 8400 84
8.5 8500 85 85
8.6 8600 86
8.7 8700 87
8.8 8800 88
8.9 8900 89
Service
wheel
LED
W2 / W3
W4 W5 W6 W7 W8
Full scale
1000
Full scale
4000
Full scale
10000
Full scale
100
Voltage
[V]
[ppm] [ppm] [ppm] [ppm] [--] [m] [--] [--] [--]
9 9000 90 90 19200 8O1
9.1 9100 91
9.2 9200 92
9.3 9300 93
9.4 9400 94
9.5 9500 95 95
9.6 9600 96
9.7 9700 97
9.8 9800 98
9.9 9900 99
10 10000 100 100 0-10 V W=1 A=1
5.4 Analog Output
The CRLDS-1000 and CRLDS-CO2 detectors features a single configurable Analog output. During normal operation, the
device’s Analog output signal is proportional to the gas concentration measured, and can be selected from the following
options:
• 1 to 5 V
• 2 to 10 V
• 0 to 10 V
• 4 to 20 mA (default)
The CRLDS-1000 and CRLDS-CO2 detectors uses different voltage/current values to indicate different operating modes.
In normal operation, the gas concentration is indicated by the Analog output signal level. The relationship between
output signal level and gas concentration is shown below:
Gas Concentration 1-5 V 2-10 V 0-10 V 4-20 mA
Underrange 2 mA
0% 1 V 2 V 0 V 4 mA
50% 3 V 6 V 5 V 12 mA
100% 5 V 10 V 10 V 20 mA
Overrange 22 mA