5.6 Magnetic Key for Configuration
The device is supplied with a magnet for
configuration. By placing it in the slot provided, the
following functions can be managed.
5.6.1 Bluetooth® Activation
After 5 seconds of exposing the magnet to the
magnetic sensor, Bluetooth® mode is activated. If
Bluetooth® is already on, after 5 seconds of exposure
Bluetooth® is deactivated.
Bluetooth® mode is automatically deactivated after
20 minutes of inactivity. Product operation in
Bluetooth® mode is indicated by the rapid flashing of
the green LED.
Bluetooth® Activation is used to set up the product
on installation and/or enter maintenance mode. When in this mode, the alarms (if present) are disabled until the normal
operating mode is restored, deactivating Bluetooth®.
5.6.2 Alarm/Warning Management
If a warning or alarm is active, after 2 seconds of exposure, the alarm will be acknowledged and deactivated. If gas is still
present, the detector will enter alarm or warning mode as usual, after a 10-second delay.
5.7 Copeland CRLDS Application Features
The CRLDS Application lets users fully exploit the potential of the new CRLDS-1000 and CRLDS-CO2 detectors, allowing
simple and intuitive interaction with the gas detector. This simplifies configuration by using a smartphone to interface
with the CRLDS-1000 and CRLDS-CO2 detector.
The Copeland CRLDS Application is available on the Google Play Store and on the App Store.
The mobile app can be used to perform the following functions:
• Configuration modify alarm thresholds, configure Modbus settings, modify relay behavior, and manage Analog output settings
• Maintenance check correct functioning of the device
• Calibration, complete with calibration report
• Display of current gas concentration measurement and indication of alarm/fault status