7.2 Gas Detected
Register 117 group Gas group Technology Default GAS Gas calibration
4 CO2 Infrared CO2 CO2
1 Mix Type 1 (R32 Blend) Semiconductor R32 R32
2 Mix Type 2 (HFC/HFO) Semiconductor R134a R134a
Gas Sensor module group Range of measurement GasType register value
R-22 2 0-1000 ppm 1
R-134a 2 0-1000 ppm 2
R-404A 2 0-1000 ppm 3
R-407C 1 0-1000 ppm 4
R-410A 1 0-1000 ppm 5
R-717 5 0-100 ppm 10
R-744 4 0-10000 ppm 11
R-407A 1 0-1000 ppm 19
R-407F 1 0-1000 ppm 22
R-32 1 0-1000 ppm 23
R-1234yf 2 0-1000 ppm 27
R-1234ze 2 0-1000 ppm 28
R-455A 1 0-1000 ppm 29
R-448A 1 0-1000 ppm 33
R-449A 1 0-1000 ppm 34
R-450A 2 0-1000 ppm 35
R-452A 1 0-1000 ppm 36
R-452B 1 0-1000 ppm 38
R-513A 2 0-1000 ppm 39
R-454B 1 0-1000 ppm 40
R-454A 1 0-1000 ppm 43
R-454C 1 0-1000 ppm 44
R-466A 1 0-1000 ppm 47
R-464A 1 0-1000 ppm 48
R-465A 1 0-1000 ppm 49
R-468A 1 0-1000 ppm 50
R-1233zde 2 0-1000 ppm 51
R-507A 1 0-1000 ppm 54