INSTALLATION, OPERATION AND MAINTENANCE MANUAL – COSA 9610™
46 | Page
4.3. TROUBLESHOOTING
Breakdown -> fault report
Test
Action
No air pressure
->
flow
alarm
For Z-purge
tube
fracture, leak in the system
Check for leak
Replace
tube
Measuring pressure
behind
reducing
valve (for z-purge)
Open valve for reducing valve
No gas pressure -> flow
alarm
Tube
fracture
Close main valve
immediately
and replace
pipe
Check/clean/replace
tubing
Oven temperature below 750°C
->
temp low
alarm
Controller. Check fuse 1 in
TB1
of regulated
supply
Reset
Check fuse 4 in TB4 of
temp.
controller (display is
off)
Replace
Check output voltage
temp.
controller (0-5 VDC) to
Solid
State
Contact
supplier
Check pulsating voltage
(0-60
VAC) to
oven
Contact
supplier
Check oven resistance ± 13 Ω
Contact
supplier
Analyzer becomes slow > 20
seconds
Check system flows and
gas
pressures
Clean system and/or adjust
to
correct
values
Check resistance of cell,
when
sample gas is “shut off” it
should
be lower than 1000 Ω
No response from
analyzer
Response to mV signal on
cell
input
terminals
Electronic problem.
Check
interface board or
computer
Response to mV signal on
cell
input
terminals
Clean systems and/or adjust
to
correct
values
Check or the test value is set
to
“NO”
Simulate mA signal
wiring.
Check test value on 0%,
25%,
Contact
supplier