CTI 2572-B / 2500C-2572-B Installation and Operation Manual 31
CHAPTER 8. START NETWORK SERVICES COMMAND
The Start Network Services command is used when you want the IP address of the2572-B module using PLC
logic. This command uses the PLC Command Interface, described in CHAPTER 7. PLC COMMAND INTERFACE
OVERVIEW. If you have selected the A
UTOSTART option, which reads the IP Parameters from flash memory,
this command is not used.
NOTE:
Before you can use PLC logic to start up the PLC network server function, the Network Startup
Option switch must be set to PLC Start (See Section 2.3. Setting the 2572-B Option Switches).
This command should be executed only when the Network Configuration Required bit (N
ET CFG) is set. The NET
CFG bit is set during a power on start or after the module is reset for any reason. It remains on until the
network parameters have been successfully set. While the 2572-B module is waiting on PLC logic to trigger
the Start Network Services command, the Network Status (NS) LED will flash.
If you have chosen the PLC Start option for network startup, you must successfully complete this
command before the 2572-B will respond to any server requests or CAMP client requests.