CTI 2572-B / 2500C-2572-B Installation and Operation Manual 74
HEX
DEC
DESCRIPTION
SOLUTION
0278
632
INVALID DEVICE CODE
The receiving device reported an invalid
device code in the message.
See error code 0273.
027A
634
INVALID DEVICE CODE
The 2572-B detected an invalid device
code in the response from the remote
device
This error may result from a transient error in
the data link. You should retry the command.
If the problem persists, check the quality of
the data link.
If the remote node is a computer simulating a
2572-B PLC server, ensure that the software
is correctly creating the response the
response message
027B
635
BAD OR MISSING DELIMITER
The 2572-B detected a missing delimiter in
the response message
See error code 027A.
027C
636
BAD BLOCK CHECK CHARACTER
The 2572-B found a bad block check
character in the response message.
See error code 027A.
027D
637
INVALID TYPE
The 2572-B detected an invalid TYPE
character in the message sent from the
remote device.
See error code 027A.
027E
638
INVALID DATA CHARACTER
The 2572-B detected an invalid data
character in the message sent from the
remote device. Only characters 0-9 and A-F
are allowed.
See error code 027A.
027F
639
ODD NUMBER OF CHARACTERS
The 2572-B detected an odd number of
characters in the message sent from the
remote device. All CAMP messages have
an even number of characters.
See error code 027A.
0280
640
UNKNOWN ERROR CHARACTER
The response contained an unknown error
character.
This error is probably caused by an
improperly programmed server node. If the
server is a PLC emulating a 2572-B server,
review the code and correct as required. If
the server is another 2572, contact CTI.
0282
642
INVALID WORD COUNT
The response contained an invalid word
count
This error is probably caused by an
improperly programmed server node. If the
server is a PLC emulating a 2572-B server,
review the code and correct as required. If
the server is another 2572, contact CTI.
0283
643
INVALID ADDRESS
The command contained a memory
address of 0.
The minimum CAMP address is 1. Enter the
correct value for the memory address.