3 — PROGRAMMABLE PARAMETERS: Fault Parameters
Fault Parameters
LOCKOUT TYPE
e Lift Lockout Type parameter denes how the controller will interpret the
lift lockout input signal at Pin J1-11. e lockout type options—Types “0”
through “3” in the Program Menu—are listed in Table 3.
Table 3 PROGRAMMABLE LIFT LOCKOUT SIGNAL TYPES
LOCKOUT
TYPE DESCRIPTION APPLICATION
0 Low = enable lockout Curtis 906, Curtis enGage™ IV
High/Open = disable lockout
1 High/Open = enable lockout Curtis 803, Curtis 841 Superspy
Low = disable lockout
2 High = enable lockout —
Low/Open = disable lockout
3 Low/Open = enable lockout —
High = disable lockout
e lockout type should be programmed appropriately for the gauge you are
using to provide lift lockout. With the Curtis 906 and enGage
™ IV, set the
lockout type to 0. With the Curtis 803 and 841 “Superspy,” set the lockout
type to 1. e other two types are available for other system congurations.
LIFT LOCK (SS1–SS4)
e lift lockout feature is designed to prevent Lift operation during undervoltage
conditions. e SS Lift Lockout parameter can be programmed On or O
independently for each of the speed select switches. When programmed On, if
Pin J1-11 receives an enable lockout signal during a Lift operation, the Lift in
progress will be completed but further Lift requests will be ignored as long as
the lockout enable signal is present. If programmed O, the Lift will continue
to operate just as if Pin J1-11 were not receiving a lockout signal.
When SS4 is used for power steering, PWM output will be shut down
when lift lockout is activated. If you do not want low battery lockout of power
steering, SS4 lift lockout should be programmed O.
THRTL LIFTLOCK
e rottle Lift Lockout parameter can be programmed On or O, and works
just like SS lift lockout. When programmed On, if Pin J1-11 receives an enable
lockout signal during a Lift operation, the Lift in progress will be completed
but further Lift requests will be ignored as long as the lockout enable signal
is present. If programmed O, the Lift will continue to operate just as if Pin
J1-11 were not receiving a lockout signal.