Model
PR750RT2U
PR1000RT2U
PR1500RT2U
PR2000RT2U
PR2200RT2U
PR3000RT2U
General
UPS Topology
Line-interactive
Energy Saving
GreenPower UPS
TM
Bypass Technology
Input
Nominal Input
Voltage
100/110/120/125V
100/110/120V
Input Voltage Range
For 110/120/125V systems: 75V 155V; For 100V systems: 70V 129V
For 110/120V systems: 75V 155V; For 100V
systems: 70V 129V
Input Frequency
50/60Hz +/- 3Hz (Auto-sensing)
Plug Type
NEMA 5-15P
NEMA 5-20P
NEMA5-30P
Power Cord Length
10ft / 3m
Output
Power Capacity
750VA/750W
1000VA/1000W
1500VA/1500W*
2000VA/2000W*
2200VA/2200W
3000VA/3000W*
On Battery Output
Voltage
100/110/120/125V +/- 5%
100/110/120V +/- 5%
On Battery Output
Frequency
50/60Hz +/- 1%
On Battery Output
Waveform
Sine Wave
Battery
Battery Type
Sealed Maintenance Free Lead Acid Battery
Replacement Battery
Pack (RBP)
RB1250X4
RB1270X4H
RB1290X4J
RBP Quantity
1
Typical Recharge Time
3 hours to 90% from total discharge under 100% load
Physical
Dimensions
2U Rack, 17.1” x 3.4” x 16.2” / 433 x 86.5 x 412 (mm)
2U Rack, 17.1” x 3.4”
x 16.7” / 433 x 86.5 x
500 (mm)
Weight
43.2lbs / 19.6kg
50.1lbs / 22.7kg
55.8lbs / 25.3kg
59.8lbs / 27.1kg
59.8lbs / 27.1kg
76.5lbs / 34.7kg
Conformance
Approvals
UL1778, CSA C22.2 No 107.3, FCC Class B, VCCI Class B, ENERGY STAR
UL1778, CSA C22.2 No 107.3, FCC Class A, VCCI
Class A, ENERGY STAR
Environmental
RoHS Compliant
*Refer below de-rating information for 100/110V systems:
PR1500RT2U: 1200VA/1200W@100V, 1350VA/1350W@110V; PR2000RT2U: 1600VA/1600W@100V, 1800VA/1800W@110V; PR3000RT2U: 2400VA/2400W@100V,