5/12
Breadcrumb Field code Setting name Range, step
Default valu
Date Value
Field settings table
Installer setting at variance with
default value
9.1.4.2 [4-0A] R/W
0: 1
1: 1/1+2 (*1) (*2)
2: 1/2
3: 1/2 + 1/1+2 in emer
9.1.4.3 [6-03] R/W 0~10kW, step: 0,2kW
2kW (*1)
3kW
9.1.4.4 [6-04] R/W 0~10kW, step: 0,2kW
4kW (*1)
6kW
└─ Main zone
9.1.5.1 [2-0C] R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.1.5.2 [C-07] R/W
0: LWT control
1: Ext RT control
2: RT control
9.1.5.3 R/W 0: Fixed
2: Weather de
9.1.5.4 R/W
0: No
1: Yes
9.1.5.5 R/W
0: 2-points
1: Slo
e-Offset
9.1.6 [1-00] R/W -40~5°C, step: 1°C
-15°C
9.1.6 [1-01] R/W 10~25°C, step: 1°C
15°C
9.1.6 [1-02] R/W
[9-01]~[9-00], step: 1°C
[2-0C]=0
35°C
[2-0C]=1
45°C
[2-0C]=2
65°C
9.1.6 [1-03] R/W [9-01]~min(45, [9-00])°C , step: 1°C
[2-0C]=0
25°C
[2-0C]=1
35°C
[2-0C]=2
35°C
9.1.7 [1-06] R/W 10~25°C, step: 1°C
20°C(*3)
9.1.7 [1-07] R/W
25~43°C, step: 1°C
35°C
9.1.7 [1-08] R/W [9-03]~[9-02]°C, step: 1°C
22°C(*3)
9.1.7 [1-09] R/W [9-03]~[9-02]°C, step: 1°C
[2-0C]=0
18°C(*3)
[2-0C]=1
7°C(*3)
[2-0C]=2
18°C(*3)
└─ Additional zone
9.1.8.1 [2-0D] R/W 0: Underfloor heating
1: Fancoil unit
2: Radiato
9.1.8.3 R/W 0: Fixed
1: WD heating, fixed cooling(*3)
2: Weather de
9.1.8.4 R/W
0: No
1: Yes
9.1.9 [0-00] R/W [9-05]~min(45,[9-06])°C, step: 1°C
35°C
9.1.9 [0-01] R/W [9-05]~[9-06]°C, step: 1°C
65°C
9.1.9 [0-02] R/W 10~25°C, step: 1°C
15°C
9.1.9 [0-03] R/W -40~5°C, step: 1°C
-15°C
9.1.A [0-04] R/W [9-07]~[9-08]°C, step: 1°C
[2-0C]=0
18°C(*3)
[2-0C]=1
7°C(*3)
[2-0C]=2
18°C(*3)
9.1.A [0-05] R/W [9-07]~[9-08]°C, step: 1°C
22°C(*3)
9.1.A [0-06] R/W 25~43°C, step: 1°C
35°C(*3)
9.1.A [0-07] R/W 10~25°C, step: 1°C
20°C(*3)
└─ Tank
9.1.B.1 [6-0D] R/W 0: Reheat only
1: Reheat + sched.
2: Scheduled onl
9.1.B.2 [6-0A] R/W 30~[6-0E]°C, step: 1°C
60°C
9.1.B.3 [6-0B] R/W 30~min(50, [6-0E])°C, step: 1°C
45°C
9.1.B.4 [6-0C] R/W 30~min(50, [6-0E])°C, step: 1°C
45°C
9.1.B.5 [6-08] R/W
2~20°C, step: 1°C
10°C
└─ Domestic hot water
9.2.1 [E-05]
[E-06]
[E-07]
R/O
3: Integrated
Reheat hysteresis
Domestic hot water
High ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT add zone cooling WD curve.
Heat up mode
Comfort setpoint
Eco setpoint
Reheat setpoint
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
High ambient temp. for LWT main zone cooling WD curve.
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
Emitter type
Setpoint mode
Schedule
WD curve type
Low ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Low ambient temp. for LWT main zone cooling WD curve.
Capacity step 1
Additional capacity step 2
Emitter type
Control
Setpoint mode
Schedule
Configuration
(*1) *6V*_(*2) *9W*_
(*3) Only applicable for models where cooling is possible_
(*4) E_(*5) E7
4P644735-1A - 2022.03