6 | Application guidelines
Installer reference guide
36
EPRA08~12EAV3+W1 + ETBH/X12EF6V+9W
Daikin Altherma 3 H MT W
4P634885-1 – 2021.03
Efficiency. Although the external room thermostat only sends ON/OFF signals, it
is specifically designed for the heatpump system.
Comfort. In case of underfloor heating, the wireless external room thermostat
prevents condensation on the floor during cooling operation by measuring the
room humidity.
Heatpump convectors
Setup
A Main leaving water temperature zone
B One single room
a Heat pump convectors (+ controllers)
For more information about connecting the electrical wiring to the unit, see:
- "9.2Connections to the outdoor unit"[4100]
- "9.3Connections to the indoor unit"[4108]
The heat pump convectors are connected as follows:
- Warm water → Indoor unit
- Cold water → Outdoor unit
The desired room temperature is set via the controller of the heat pump
convectors. There are different controllers and setups possible for the heat pump
convectors. For more information, see:
- The installation manual of the heat pump convectors
- The installation manual of the heat pump convector options
- The addendum book for optional equipment
The space heating/cooling demand signal is sent to one digital input on the
indoor unit (X2M/35 and X2M/30).
The space operation mode is sent to the heat pump convectors by one digital
output on the indoor unit (X2M/4 and X2M/3).
Configuration
Setting Value
Unit temperature control:
#: [2.9]
Code: [C-07]
1 (External room thermostat):
Unit operation is decided by the
external thermostat.