9 | Electrical installation
Installer reference guide
138
ERLA11~16D + EBVH16SU23D
Daikin Altherma 3 R F
4P655196-1A – 2022.05
1+2 Wires connected to the space
cooling/heating ON/OFF output
3 Wire between X2M and A4P
A4P Installation of EKRP1HBAA is
required.
a Installation of EKRP1HBAA is required.
b Prewiring between X2M/7+9 and Q1L (=thermal protector backup heater). Do NOT
change.
3 Fix the cable with cable ties to the cable tie mountings.
9.3.8 To connect the changeover to external heat source
INFORMATION
Bivalent is only possible in case of 1 leaving water temperature zone with:
▪ room thermostat control, OR
▪ external room thermostat control.
Wires: 2×0.75mm²
Maximum load: 0.3A, 250VAC
Minimum load: 20mA, 5VDC
[9.C] Bivalent