15 | Troubleshooting
Installer reference guide
270
ERLA11~16D + EBVH16SU23D
Daikin Altherma 3 R F
4P655196-1A – 2022.05
15.3.9 Symptom: The space is NOT sufficiently heated at low outdoor temperatures
Possible causes Corrective action
The backup heater operation is not
activated
Check the following:
The backup heater operation mode is
enabled.
Go to: [9.3.8]: Installer
settings > Backup heater >
Operation [4‑00]
The backup heater overcurrent circuit
breaker is on. If not, turn it back on.
The thermal protector of the backup
heater is NOT activated. If it has,
check the following, and then press
the reset button in the switch box:
- The water pressure
- Whether there is air in the system
- The air purge operation
The backup heater equilibrium
temperature has not been configured
correctly
Increase the equilibrium temperature to
activate the backup heater operation at
a higher outdoor temperature.
Go to: [9.3.7]: Installer settings
> Backup heater > Equilibrium
temperature [5‑01]
There is air in the system. Purge air manually or automatically. See
the air purge function in the chapter
"12Commissioning"[4245].
Too much heat pump capacity is used
for heating domestic hot water
Check if the Space heating
priority settings have been
configured appropriately:
Make sure that the Space heating
priority has been enabled.
Go to [9.6.1]: Installer
settings > Balancing > Space
heating priority [5‑02]
Increase the "space heating priority
temperature" to activate backup
heater operation at a higher outdoor
temperature.
Go to [9.6.3]: Installer
settings > Balancing >
Priority temperature [5‑03]