EasyManua.ls Logo

Daikin Altherma 3 R F - Recovery Mode - in Case of 1 N~ Models (7-Leds Display)

Daikin Altherma 3 R F
312 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16 | Disposal
Installer reference guide
282
ERLA11~16D + EBVH16SU23D
Daikin Altherma 3 R F
4P655196-1A – 2022.05
16.1.4 Recovery mode — In case of 1N~ models (7-LEDs display)
Before recovering refrigerant, make sure the electronic expansion valves are open.
When power is ON, this has to be done by using the recovery mode.
Components
To activate/deactivate the recovery mode, you need the following components:
BS2
SET
BS1
MODE
BS3
RETURN
BS4
PUMP DOWN
H1P H2P H3P H4P H5P H6P H7P
DEMANDL.N.O.P.HWLMODE TEST
1N~
H1P~H7P 7‑LEDs display
BS1~BS4 Push buttons. Operate the push buttons with an insulated stick (such as a closed
ballpoint pen) to avoid touching of live parts.
1N~
BS2
SET
BS1
MODE
BS3
RETURN
BS4
PUMP DOWN
H1P H2P H3P H4P H5P H6P H7P
DEMANDL.N.O.P.HWLMODE TEST
H1P~H7P 7‑LEDs display
BS1~BS4 Push buttons. Operate the push buttons with an insulated stick (such as a closed
ballpoint pen) to avoid touching of live parts.
To activate the recovery mode
INFORMATION
If you get confused in the middle of the process, press BS1 to return to the default
situation.
Before recovering refrigerant, activate the recovery mode as follows:

Table of Contents

Other manuals for Daikin Altherma 3 R F

Related product manuals