9 | Electrical installation
Installer reference guide
142
ERLA11~16D + EBVH16SU23D
Daikin Altherma 3 R F
4P655196-1A – 2022.05
Smart Grid contact Smart Grid operation mode
1
2
0 1 Forced off
1 0 Recommended on
1 1 Forced on
The use of a Smart Grid pulse meter is not mandatory:
If Smart Grid pulse meter is… Then [9.8.8] Limit setting kW is…
Used
([9.A.2] Electricity meter 2
None)
Not applicable
Not used
([9.A.2] Electricity meter 2 =
None)
Applicable
In case of low voltage Smart Grid contacts
Wires (Smart Grid pulse meter): 0.5mm²
Wires (low voltage Smart Grid contacts): 0.5mm²
[9.8.4]=3 (Benefit kWh power supply = Smart grid)
[9.8.5] Smart grid operation mode
[9.8.6] Allow electrical heaters
[9.8.7] Enable room buffering
[9.8.8] Limit setting kW
The wiring of the Smart Grid in case of low voltage contacts is as follows:
1413
S11S
65
S4S
43
X5M
S10S
109
a
2 1
a Jumper (factory-mounted). If you also connect a safety thermostat (Q4L), replace
the jumper with the safety thermostat wires.
S4S Smart Grid pulse meter
1
/S10S Low voltage Smart Grid contact 1
2
/S11S Low voltage Smart Grid contact 2
1 Open the following (see "7.2.4To open the indoor unit"[479]):
1 Top panel
1
2
3
2 User interface panel
3 Upper switch box cover
2 Connect the wiring as follows: