11 | Configuration
Installer reference guide
161
ERLA11~16D + EBVH16SU23D
Daikin Altherma 3 R F
4P655196-1A – 2022.05
Schedule/Control Description
[3.2] Additional zone >
Heating schedule
Schedule for when the system
is allowed to heat up the
additional zone in heating
mode.
Predefined schedules: 1
Activation screen: [3.1] Schedule
Possible actions:
▪ Off: When the system is NOT allowed to heat
up the additional zone.
▪ On: When the system is allowed to heat up the
additional zone.
[3.3] Additional zone >
Cooling schedule
Schedule for when the system
is allowed to cool down the
additional zone in cooling
mode.
Predefined schedules: 1
Activation screen: [3.1] Schedule
Possible actions:
▪ Off: When the system is NOT allowed to cool
down the additional zone.
▪ On: When the system is allowed to cool down
the additional zone.
[4.2] Space heating/
cooling > Operation mode
schedule
Schedule (per month) for when
to operate the unit in heating
mode and when in cooling
mode.
See "To set the space operation mode"[4194].
[5.5] Tank > Schedule
Schedule for the domestic hot
water tank temperature for
your normal domestic hot
water needs.
Predefined schedules: 1
Activation screen: Not applicable. This schedule
is automatically activated if the DHW mode is
one of the following:
▪ Schedule only
▪ Schedule + reheat
Possible actions:
▪ Comfort: When to start heating the tank to
the user-defined preset value [5.2] Comfort
setpoint.
▪ Eco: When to start heating the tank to the
user-defined preset value [5.3] Eco
setpoint.
▪ Stop: When to stop heating the tank, even if
the desired tank temperature is not reached
yet.
Note: In Schedule + reheat mode, the
system also takes the user-defined preset value
[5.4] Reheat setpoint into account.