11 | Configuration
Installer reference guide
179
ERLA11~16D + EBVH16SU23D
Daikin Altherma 3 R F
4P655196-1A – 2022.05
Main zone
Additional zone
Room
Malfunctioning
Space heating/cooling
[2] Main zone
Setpoint screen
[2.1] Schedule
[2.2] Heating schedule
[2.3] Cooling schedule
[2.4] Setpoint mode
[2.5] Heating WD curve
[2.6] Cooling WD curve
[2.7] Emitter type
[2.8] Setpoint range
[2.9] Control
[2.A] Ext thermostat type
[2.B] Delta T
[2.C] Modulation
[2.D] Shut off valve
[2.E] WD curve type
Setpoint screen
Control the leaving water temperature for the main zone via setpoint screen [2]
Main zone.
See "11.3.5Setpoint screen"[4157].
Schedule
Indicate if the temperature of the leaving water is defined according to a schedule
or not.
Influence of the LWT setpoint mode [2.4] is as follows:
▪ In Fixed LWT setpoint mode, the scheduled actions consist of desired leaving
water temperatures, either preset or custom.
▪ In Weather dependent LWT setpoint mode, the scheduled actions consist of
desired shift actions, either preset or custom.
# Code Description
[2.1] N/A Schedule:
▪ 0: No
▪ 1: Yes
Heating schedule
Define a heating temperature schedule for the main zone via [2.2] Heating
schedule.
See "11.4.3Schedule screen: Example"[4162].
Cooling schedule
Define a cooling temperature schedule for the main zone via [2.3] Cooling
schedule.
See "11.4.3Schedule screen: Example"[4162].