11 | Configuration
Installer reference guide
183
ERLA11~16D + EBVH16SU23D
Daikin Altherma 3 R F
4P655196-1A – 2022.05
# Code Description
[2.7] [2‑0C] Emitter type:
0: Underfloor heating
1: Fancoil unit
2: Radiator
The setting Emitter type influences the space heating setpoint range and the
target delta T in heating as follows:
Emitter type Main
zone
Space heating setpoint
range [9‑01]~[9‑00]
Target delta T in heating
[1‑0B]
0: Underfloor
heating
Maximum 55°C Variable (see [2.B.1])
1: Fancoil unit Maximum 55°C Variable (see [2.B.1])
2: Radiator Maximum 60°C Fixed 8°C
NOTICE
The maximum setpoint in space heating depends on the emitter type as can be seen
in above table. If there are 2 water temperature zones, then the maximum setpoint
is the maximum of the 2 zones.
NOTICE
NOT configuring the system in the following way can cause damage to the heat
emitters. If there are 2 zones, it is important that in heating:
the zone with the lowest water temperature is configured as the main zone, and
the zone with the highest water temperature is configured as the additional zone.
NOTICE
If there are 2 zones and the emitter types are wrongly configured, water of high
temperature can be sent towards a low temperature emitter (underfloor heating). To
avoid this:
Install an aquastat/thermostatic valve to avoid too high temperatures towards a
low temperature emitter.
Make sure you set the emitter types for the main zone [2.7] and for the
additional zone [3.7] correctly in accordance with the connected emitter.
NOTICE
Average emitter temperature = Leaving water temperature – (Delta T)/2
This means that for a same leaving water temperature setpoint, the average emitter
temperature of radiators is lower than that of underfloor heating because of a bigger
delta T.
Example radiators: 40–8/2=36°C
Example underfloor heating: 40–5/2=37.5°C
To compensate, you can:
Increase the weather-dependent curve desired temperatures [2.5].
Enable leaving water temperature modulation and increase the maximum
modulation [2.C].