11 | Configuration
Installer reference guide
228
ERLA11~16D + EBVH16SU23D
Daikin Altherma 3 R F
4P655196-1A – 2022.05
# Code Description
[9.9.3] [5-05] Limit: Only applicable in case of full time
current limitation mode.
0A~50A
Limits when [9.9.1]=Inputs and [9.9.2]=Amp:
# Code Description
[9.9.4] [5-05] Limit 1: 0A~50A
[9.9.5] [5-06] Limit 2: 0A~50A
[9.9.6] [5-07] Limit 3: 0A~50A
[9.9.7] [5-08] Limit 4: 0A~50A
Limit when [9.9.1]=Continuous and [9.9.2]=kW:
# Code Description
[9.9.8] [5-09] Limit: Only applicable in case of full time
power limitation mode.
0kW~20kW
Limits when [9.9.1]=Inputs and [9.9.2]=kW:
# Code Description
[9.9.9] [5-09] Limit 1: 0kW~20kW
[9.9.A] [5-0A] Limit 2: 0kW~20kW
[9.9.B] [5-0B] Limit 3: 0kW~20kW
[9.9.C] [5-0C] Limit 4: 0kW~20kW
Priority heater
This setting defines the priority of the electrical heaters depending on applicable
limitation. As no booster heater is present, the backup heater will always be
prioritised.
# Code Description
[9.9.D] [4-01] Priority heater:
0 None : The backup heater is prioritised.
1 Booster heater: After restart, the
setting will be reverted back to 0=None and
the backup heater will be prioritised.
2 Backup heater: The backup heater is
prioritised.
BBR16
See "6.6.4 BBR16 power limitation" [4 61] for detailed information about this
functionality.
INFORMATION
Restriction: BBR16 settings are only visible when the language of the user interface is
set to Swedish.