16 | Disposal
Installer reference guide
280
ERLA11~16D + EBVH16SU23D
Daikin Altherma 3 R F
4P655196-1A – 2022.05
# Action 7-segments display
(a)
1 Start from the default situation.
2 Select mode 2.
Press and hold BS1 for 5seconds.
3 Select setting 9.
Press BS2 9times.
4 Select value 2.
a Display the current value.
Press BS3 once.
b Change the value to 2.
Press BS2 once.
c Enter the value in the system.
Press BS3 once.
d Confirm.
Press BS3 once.
5 Return to the default situation.
Press BS1 once.
(a)
= OFF, = ON, and = flashing.
Result: The recovery mode is activated. The unit opens the electronic expansion
valves.
To deactivate the recovery mode
After recovering refrigerant, deactivate the recovery mode as follows:
# Procedure 7-segments display
(a)
1 Start from the default situation.
2 Select mode 2.
Press and hold BS1 for 5seconds.
3 Select setting 9.
Press BS2 9times.
4 Select value 1.