FTX-N/U, FVXS-N, FDMQ-R Series EDUS091558E
99
C: 3P379970-7B
7
Indoor Unit Installation
2. Drilling a wall hole and installing wall embedded pipe
WARNING
For metal frame or metal board walls, be sure to use a wall embedded pipe and wall hole cover in the feed-through hole to
prevent possible heat, electric shock, or re.
• Be sure to caulk the gaps around the pipes with caulking material to prevent
condensation.
1) Drill a feed-through hole with a φ2-9/16 inch (65mm) diameter through the
wall at a downward angle toward the outside.
2) Insert a wall embedded pipe into the hole.
3) Insert a wall hole cover into wall pipe.
4) After completing refrigerant piping, wiring, and drain piping, caulk the pipe
hole gap with putty.
Inside
Outside
Caulking
(eld supply)
Wall embedded
pipe
(eld supply)
Wall hole cover
(eld supply)
φ2-9/16”
(65mm)
3. Drain piping
• The drain pipe should be inclined downward so that water will ow smoothly
without any accumulation. (Should not be trap.)
No trap is permitted.
The drain pipe should
be inclined downward.
Do not put the end
of the hose in water.
• Use commercial rigid polyvinyl chloride pipe (general VP 20 pipe, outer diameter 1 inch (26mm), inner diameter 13/16
inch (20mm)) for the drain pipe.
• The drain hose (outer diameter φ11/16 inch (φ18mm) at connecting end, 8-11/16 inch (220mm) long) is supplied with the
indoor unit.
1) Perform drain piping work as outlined in the gure. (See Fig. 1)
• Insert the
C
drain hose into the socket of the drain pan. (See Fig. 2)
Fully insert the drain hose until it adheres to a seal of the socket.
2) Insulate the indoor drain pipe with 3/8 inch (10mm) or more of insulation material to prevent condensation.
3) Remove the air lters and pour some water into the drain pan to check the water ows smoothly.
1-15/16
(50) or more
8-11/16 (220)
5-7/8
(150)
3-15/16
(100)
3-15/16 (100)
Reducer
Vinyl chloride
drain pipe
(VP-30)
Vinyl chloride
drain pipe
(VP-20)
Drain hose
C
unit: inch (mm)
Insert drain hose
to this depth so
it won’t be pulled
out of drain pipe.
Drain
pan
Drain pan
Seal
Seal
Drain hose
C
Drain hose
C
Fig. 1 Fig. 2
CAUTION
Use polyvinyl chloride adhesive agent for gluing. Failure to do so may cause water leakage.
01_EN_3P379970-7B.indd 7 11/12/2015 13:29:43