EasyManua.ls Logo

Daikin FTX-N/U - Wiring

Daikin FTX-N/U
484 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
174
FTX-N/U, FVXS-N, FDMQ-R Series EDUS091558E
3P379970-10C
9
Wiring
WARNING
Donotusetappedwires,extensioncords,orstarburstconnections,astheymaycauseoverheating,electricshock,orre.
Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the
terminalblock.)Doingsomaycauseelectricshockorre.
Be sure to install a ground fault circuit interrupter. (One that can handle higher harmonics.)
(This unit uses an inverter. Therefore, a ground fault circuit interrupter capable of handling higher harmonics must be used in
order to prevent the ground fault circuit interrupter malfunctioning.)
Use an all-pole disconnection type circuit breaker with at least 1/8 inch (3mm) between the contact point gaps.
When carrying out wiring, take care not to pull at the conduit.
Donotconnectthepowerwiretotheindoorunit.Doingsomaycauseelectricshockorre.
Do not turn on the circuit breaker until all work is completed.
1) Strip the insulation from the wire (3/4 inch (20mm)).
2) Connect the inter-unit wires between the indoor and outdoor units so that the terminal numbers match. Tighten the
terminalscrewssecurely.Itisrecommendedthataatheadscrewdriverbeusedtotightenthescrews.
The screws are packed with the terminal block.
1
2
3
123
Circuit
breaker
Ground fault
circuit interrupter
Ground
Firmlyxthewireswith
theterminalscrews.
UseAWG16iftheconnectionwire
lengthislessthan33ft(10m),or
AWG14ifitis33ft(10m)ormore.
Outdoor unit
Indoor
unit
Powersupply
60Hz208-230V
Firmlyxthe
wireswiththe
terminalscrews.
UseAWG14wires.
RX09/12,RK09/12
RXN09/12/18,RKN09/12/18,RXL09/12/15
RX18/24,RK18/24
RXN24,RKN24
15A
20A
L
1
L
2
09/12 class
[Method of mounting conduit]
•Aprotectionplateisxedforprotectionfromthehigh-voltagesection.
1) Dismount the stop valve cover by removing the screw.
2) Dismount the protection plate by removing the 2 screws.
3) Dismount the conduit mounting cover by removing the 2 screws.
4) Pass wires through the conduit and secure them with a lock nut.
5) After completing the work, reattach the stop valve cover, the conduit mounting cover, and the protection plate to its
original position.
1
2
3
1
2
3
1
2
3
Screws
Conduit
mounting
cover
Screws
Protection plate
Power supply
terminal block
Shape wires so
that the protection
plate and conduit
mountingplatet
securely.
Conduit
Lock nut
Conduit
mounting
plate
L
1
L
2
01_EN_3P379970-10C.indd 9 10/18/2019 9:18:01 AM

Table of Contents

Related product manuals