EasyManua.ls Logo

Daikin FTX-N/U - Page 118

Daikin FTX-N/U
484 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
116
FTX-N/U, FVXS-N, FDMQ-R Series EDUS091558E
3P500432-1
CAUTION
Install the indoor unit leveled.
If the indoor unit is inclined and the drain piping side gets
high,itmaycausemalfunctionofoatswitchandresultin
water leakage.
Attach nuts on the upper and lower side of hanger.
If there is no upper nut and the lower nut is over-tightened,
the hanger and the top plate will deform and cause abnormal
sound.
Donotinsertmaterialsotherthanthatspeciedinto
the clearance between the hanger and the washer for
hanger bracket (11).
Unless the washers are properly attached, the
suspension bolts may come off from the hanger.
WARNING
The indoor unit must be securely installed on a place
that can withstand the mass.
Ifthestrengthisinsufcient,theindoorunitmayfalldown
and cause injuries.
6. REFRIGERANT PIPING WORK
Refer to the installation manual for the outdoor unit also.
Carry out insulation of both gas and liquid refrigerant piping
securely. If not insulated, it may cause water leakage. For
gas piping, use insulation material of which heat resistant
temperature is not less than 230°F (110°C).
For use under high humidity, strengthen the insulation
material for refrigerant piping. If not strengthened, the
surface of insulation material may sweat.
(1) Flaring the pipe end
1. Cut the pipe end with a pipe cutter.
2. Remove burrs with the cut surface facing downward,
sothatthelingsdonotenterthepipe.
3.Putthearenutonthepipe.
4. Flare the pipe.
5.Checkthatthearinghasbeendonecorrectly.
Theare’sinnersurface
mustbeaw-free.
Thepipeendmust
beevenlyaredina
perfectcircle.
Makesurethatthe
arenutistted.
Check
A
Cutexactlyatrightangles. Removeburrs
Setexactlyatthepositionshownbelow.
A
0-0.02in
(0-0.5mm)
0.04-0.06in
(1.0-1.5mm)
0.06-0.08in
(1.5-2.0mm)
Clutch-type
FlaretoolforR410A
Clutch-type
(Rigid-type)
Wing-nuttype
(Imperial-type)
Conventionalaretool
Flaring
Die
WARNING
Donotapplymineraloiltotheare.
Prevent mineral oil from getting into the system as
this would reduce the service life of the units.
Never use piping which has been used for previous
installations. Only use parts which are delivered with this unit.
Never install a dryer to this R410A unit in order to
guarantee its service life.
The drying material may dissolve and damage the system.
Incompletearingmayresultinrefrigerantgasleakage.
CAUTION
•Usethearenutxedtothemainunit.(Thisisto
preventthearenutfromcrackingasaresultof
deterioration over time.)
Useapipecutterandaresuitableforthetypeof
refrigerant.
To prevent gas leakage, apply refrigeration oil only to
theinnersurfaceoftheare.(Userefrigerationoilfor
R410A.) (Refer to Fig. 10)
Useatorquewrenchwhentighteningthearenutsto
preventdamagetothearenutsandgasleakage.
Protect the open end of the pipe against dust and moisture.
Do not allow anything other than the designated
refrigerant to get mixed into the refrigerant circuit, such
as air, etc. If any refrigerant gas leaks while working on
the unit, ventilate the room thoroughly right away.
Useonlythearenutsattachedtotheairconditioner.If
otherarenutsareused,itmaycauserefrigerantleakage.
(2) Refrigerant piping
1. To prevent gas leakage, apply refrigeration machine
oilonlytotheinnersurfaceoftheare.(Use
refrigeration oil for R410A)
2. Alignthecentersofbotharesandtightentheare
nuts 3 or 4 turns by hand, then tighten them fully with
a spanner and a torque wrench.
Useatorquewrenchwhentighteningthearenuts
topreventdamagetothearenutsandgasleakage.
(Refer to Fig. 9)
Flare nut tightening torque
Gas side Liquid side
3/8 inch
(9.5mm)
1/2 inch
(12.7mm)
5/8 inch
(15.9mm)
1/4 inch
(6.4mm)
24.1-29.4ft•lbf
(32.7-39.9N•m)
36.5-44.5ft•lbf
(49.5-60.3Nm)
45.6-55.6ft•lbf
(61.8-75.4Nm)
10.4-12.7ftlbf
(14.2-17.2N•m)
7
01_EN_3P500432-1.indd 7 10/24/2017 18:32:33

Table of Contents

Related product manuals