FTX-N/U, FVXS-N, FDMQ-R Series EDUS091558E
183
3P572321-4B
6
3. Flaring the pipe end
WARNING
Donotapplymineraloiltotheare.
Prevent mineral oil from getting into the system as this would reduce the service life of the units.
Never use piping which has been used for previous installations. Only use parts which are delivered with this unit.
Never install a dryer to this R410A unit in order to guarantee its service life.
The drying material may dissolve and damage the system.
Incompletearingmayresultinrefrigerantgasleakage.
CAUTION
Do not reuse joints which have been used once already.
1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing
downward,sothatthelingsdonotenterthe
pipe.
3) Putthearenutonthepipe.
4) Flare the pipe.
5) Checkthatthearinghasbeendonecorrectly.
Check
Thearesinner
surfacemustbe
aw-free.
Whenaring,do
notover-tighten
andcrack.
Thepipeendmust
beevenlyaredin
aperfectcircle.
Makesurethatthe
arenutistted.
Setexactlyatthepositionshownbelow.
Flaring
A
Die
A
0-0.020inch
(0-0.5mm)
Clutch-type
FlaretoolforR410A
0.039-0.059inch
(1.0-1.5mm)
Clutch-type(Rigid-type)
0.059-0.079inch
(1.5-2.0mm)
Wing-nuttype(Imperial-type)
Conventionalaretool
Cutexactlyat
rightangles.
Removeburrs.
4. Refrigerant piping
CAUTION
Usethearenutxedtothemainunit.(Thisistopreventthearenutfromcrackingasaresultofdeteriorationovertime.)
Topreventgasleakage,applyrefrigerationoilonlytotheinnersurfaceoftheare.(UserefrigerationoilforR410A.)
Useatorquewrenchwhentighteningthearenutstopreventdamagetothearenutsandgasleakage.
Alignthecentersofbotharesandtightenthearenuts3or4turnsbyhand,thentightenthemfullywithaspanneranda
torque wrench.
Do not apply refrigeration
oil to the outer surface.
Flare nut
Apply refrigeration
oil only to the inner
surfaceoftheare.
Do not apply refrigeration oil to
thearenuttoavoidtightening
withexcessivetorque.
Apply oil
Torquewrench
Piping union
Flare nut
Spanner
Tighten
01_EN_3P572321-4B.indd 6 2019/10/17 14:46:59