Troubleshooting SiBE01-829
54 Service Diagnosis
Troubleshooting
Check No.06
Refer to P.55
(R8644)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
YES
Malfunctioning
NO
NO
YES
YES
YES
NO
Functioning
YES
NO
NO
NO
YES
* Indoor heat exchanger thermistor
Check for gas leakage.
Change for a specified amount of
fresh refrigerant.
Replace in position.
Open the stop valve.
Repair the pipe flare or
replace the square union.
Check the power transistor
harness for looseness.
Correct it as required. Also
replace cracked pipe if any.
Check the pipes for
improper contact. Correct
as required. Also replace
cracked pipe if any.
Replace the indoor unit heat
exchanger thermistor.
(1) Replace the PCB.
(2) Replace the
compressor.
Procedure complete
Gas shortage error again?
Oil oozing at internal
piping?
Stop valve closed?
Compressor vibrating
too much?
Oil oozing at relay
pipe connections?
Is thermistor
disconnected?
Check No. 06
Check the thermistors.

Table of Contents

Other manuals for Daikin FTYN35GXV1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FTYN35GXV1B and is the answer not in the manual?

Daikin FTYN35GXV1B Specifications

General IconGeneral
BrandDaikin
ModelFTYN35GXV1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals