Variable Compressor Set-up
Table 25: Variable Compresor Setup Menu
Item Display Name Default Setting Range Password Level
Compressor Status
Var Cmp Status=
OFF
4
ON
Var Spd Cmd= 0–100% 4
Comp 1=
OFF
4
ON
Comp 3=
OFF
4
ON
Comp 5=
OFF
4
ON
Refrig Circuit Status
PTD1= 0–5000kPa 4
PTD2= 0–5000kPa 4
VCmpDischSH= -100.0–100.0°F 4
C1DschSatTmp= -50.0–212.0°F 4
C2DschSatTmp= -50.0–212.0°F 4
DRT1= -50.0–392.0°F 6
DRT2= -50.0–392.0°F 6
Cond Sol 1= OFF
OFF
4
ON
Cond Sol 2= OFF
OFF
4
ON
Compressor Setup
Var Cmp Period= 20s 1–300s 4
Var Cmp Gain= 1 0.0–100.0 4
Var Cmp PAT= 40s 0–999s 4
VarCmp MaxChg= 10% 0–50% 4
OilBoost= OFF
OFF
2
ON
LowOilTime= 10m 1–30m 2
OilBoostTime= 15m 1–15m 2
LowTcOAT= 80°F 50–122°F 2
OM 920-6 • MICROTECH UNIT CONTROLLER 42 www.DaikinApplied.com
Menu desCrIpTIons