EasyManuals Logo

Daikin MicroTech III User Manual

Daikin MicroTech III
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #42 background imageLoading...
Page #42 background image
Variable Compressor Set-up
Table 25: Variable Compresor Setup Menu
Item Display Name Default Setting Range Password Level
Compressor Status
Var Cmp Status=
OFF
4
ON
Var Spd Cmd= 0–100% 4
Comp 1=
OFF
4
ON
Comp 3=
OFF
4
ON
Comp 5=
OFF
4
ON
Refrig Circuit Status
PTD1= 0–5000kPa 4
PTD2= 0–5000kPa 4
VCmpDischSH= -100.0–100.0°F 4
C1DschSatTmp= -50.0–212.0°F 4
C2DschSatTmp= -50.0–212.0°F 4
DRT1= -50.0–392.0°F 6
DRT2= -50.0–392.0°F 6
Cond Sol 1= OFF
OFF
4
ON
Cond Sol 2= OFF
OFF
4
ON
Compressor Setup
Var Cmp Period= 20s 1–300s 4
Var Cmp Gain= 1 0.0–100.0 4
Var Cmp PAT= 40s 0–999s 4
VarCmp MaxChg= 10% 0–50% 4
OilBoost= OFF
OFF
2
ON
LowOilTime= 10m 1–30m 2
OilBoostTime= 15m 1–15m 2
LowTcOAT= 80°F 50–122°F 2
OM 920-6 • MICROTECH UNIT CONTROLLER 42 www.DaikinApplied.com
Menu desCrIpTIons

Table of Contents

Other manuals for Daikin MicroTech III

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech III and is the answer not in the manual?

Daikin MicroTech III Specifications

General IconGeneral
BrandDaikin
ModelMicroTech III
CategoryController
LanguageEnglish

Related product manuals