Dehum Set-Up
Table 29: Dehumidication Menu
Item Display Name Default Setting Range Password Level
Dehum Method= None
None
4
Rel Hum
DewPt
Always
RH DB= 2% 0–10% 4
Dewpoint DB= 2.0°F 2–10°F 4
RH Period= 30s 0–999s 4
RH Gain= 1 0.0–100.0 4
RH PAT= 30s 0–999s 4
RH Max Chg= 10% 0–100% 4
LSC Lo Gain= 0.2 0.0–100.0 2
RH Stg Time= 10min 0–60min 4
Stg Rht DB= 5°F 0–20°F 4
Dehum Ctrl= Occupied
Occupied
4
Always
Sensor Loc= Return
Return
4OAT
Space
Mn Lvg Coil T= 45.0°F 40–100°F 4
Mx Lvg Coil T= 52.0°F 40–100°F 4
Rht Cmp Lmtg= Yes
No
Yes
2
Min Rheat Spt= 55.0°F 40.0–100.0°F 4
Max Rheat Spt = 65.0°F 40.0–100.0°F 4
RH Sens Type= VDC
VDC
mA
2
RH Min Sig= 0.0V
0.0–20.0
2
V/mA
RH Max Sig= 10.0V
0.0–20.0
2
V/mA
Min Dehum Spd= 33% 0–100% 2
Max Dehum Spd= 100% 0–100% 2
Rht Min Pos=
10% (RPS)
0–100% 2
15% (MPS, DPS, DPH)
RH Dec Rate= 1 0–10.00%/s 2
Menu desCrIpTIons
www.DaikinApplied.com 51 OM 920-6 • MICROTECH UNIT CONTROLLER