Manual Control
The manual control of operation is a function that is used for operating the unit during a service call only. The unit must not be
operated in this mode for any extended period of time.
Table 36: Manual Control Menu
Item Display Name Default Setting Range Password Level
Manual Ctrl= Normal
Normal
4
ManCtrl
Supply Fan=
OFF
OFF
4
ON
SAF Spd Cmd= 0% 0–100% 4
RF/EF VFD= OFF
OFF
4
ON
RF/EF Spd Cmd= 0% 0–100% 4
OAD/Econo= 0% 0–100% 4
OAD OpCl= Close
Close
4
Open
Var Cmp= OFF
OFF
4
ON
Var Cmp Cmd= 0% 0–100% 4
VCmp Emg Stop= Nrml
Stop
4
Normal
Comp 1 = OFF
OFF
4
ON
Comp 2 = OFF
OFF
4
ON
Comp 3 = OFF
OFF
4
ON
Comp 4 = OFF
OFF
4
ON
Comp 5 = OFF
OFF
4
ON
Comp 6 = OFF
OFF
4
ON
Comp 7 = OFF
OFF
4
ON
Comp 8 = OFF
OFF
4
ON
U1 Comp 1= OFF
OFF
4
ON
U1 Comp 2= OFF
OFF
4
ON
U2 Comp 1= OFF
OFF
4
ON
U2 Comp 2= OFF
OFF
4
ON
Cond Sol 1= OFF
OFF
4
ON
Cond Sol 2= OFF
OFF
4
ON
Cfan Outpt 1= OFF
OFF
4
ON
Cfan Outpt 2= OFF
OFF
4
ON
Cfan Outpt 3= OFF
OFF
4
ON
BP/WR Valve= 0% 0–100% 4
CW Valve= 0% 0–100% 4
ExhFan Out 1= OFF
OFF
4
ON
ExhFan Out 2= OFF
OFF
4
ON
ECond VFD= OFF
OFF
4
ON
ECFan Spd Cmd= 0% 0–100% 4
EC Drn Valve= Close
Close
4
Open
Sump Pump= OFF
OFF
4
ON
Sep Flsh Vlv= OFF
OFF
4
ON
SV1= OFF
OFF
4
ON
SV2= OFF
OFF
4
ON
Menu desCrIpTIons
www.DaikinApplied.com 59 OM 920-6 • MICROTECH UNIT CONTROLLER