Sensor Offsets Menu
The Sensor Offsets Menu provides a means of calibrating the
various temperature sensor inputs to the unit. Each sensor
can be “biased” by as much as +/- 10.0°F.
Table 47: Sensor Offset Menu
Item Display Name Default Setting Range Password Level
Disch Air= 0.0°F 0.0–10.0°F 2
Return Air= 0.0°F 0.0–10.0°F 2
SpaceTemp= 0.0°F 0.0–10.0°F 2
OA Temp= 0.0°F 0.0–10.0°F 2
ER LAT= 0.0°F 0.0–10.0°F 2
ER EAT= 0.0°F 0.0–10.0°F 2
DRT1= 0.0°F -10.0–10.0°C 2
DRT2= 0.0°F -10.0–10.0°C 2
OM 920-6 • MICROTECH UNIT CONTROLLER 68 www.DaikinApplied.com