Si-71A Thermistor Temperature and Resistance Conversion Table
Explanation of Function Operation 61
4. Thermistor Temperature and Resistance Conversion Table
4.1 Table
Temperature (°C)
Suction, Heat Exchange (Indoor
Unit), Outdoor Air, Outdoor Suction
Pipe, Sensor (k
)
Discharge Pipe Sensor (k
)
-6.0 90.8 866.8
-4.0 81.7 782.7
-2.0 73.5 707.6
0.0 66.3 640.4
2.0 59.8 579.9
4.0 54.1 525.6
6.0 48.9 477.0
8.0 44.3 433.4
10.0 40.2 394.2
12.0 36.5 358.9
14.0 33.2 327.1
16.0 30.2 298.5
18.0 27.5 272.6
20.0 25.1 249.2
22.0 23.0 228.1
24.0 21.0 208.9
26.0 19.2 191.5
28.0 17.6 175.8
30.0 16.2 161.5
32.0 14.8 148.4
34.0 13.6 136.6
36.0 12.5 125.8
38.0 11.5 115.5
40.0 10.6 106.5
42.0 9.8 98.8
44.0 9.1 91.3
46.0 8.4 84.4
48.0 7.8 78.1
50.0 7.2 72.3
52.0 6.9 67.1
54.0 6.2 62.2
56.0 5.7 57.8
58.0 5.3 53.7