EasyManuals Logo

Daikin VRV III User Manual

Daikin VRV III
455 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
Features ED34-862
16 General Information
Large capacities for large-sized buildings
Piping length is drastically extended! The long piping length provides more design flexibility, which can match
even large-sized buildings.
Extended long piping length
VRVII MA series
150 m
165 m
175 m
190 m
510 m
1000
m
Max. equivalent piping length
Max. actual piping length
50 m
40 m
VRVII MA series
VRVII MA series
VRVII MA series
p
q
k
First outdoor branch
f
a
b
First
indoor branch
Multiple use
*The rest of indoor units are
the same as for single use.
a
i
s
r
h
g
f
e
d
c
b
First indoor branch
Single use
Colours in the diagram above are merely for identifying pipes referenced with symbols such as a .
Max. total piping length
Max. level difference
between the outdoor units
and the indoor units
Outdoor unit
above indoor unit:
Outdoor unit above indoor unit:
2. Level differences above 50 m
are available on request.
Outdoor unit below indoor unit:
Outdoor unit above indoor unit:
Outdoor unit below indoor unit:
Outdoor unit
below indoor unit:
90
m
2
RXQ8PA-54PA
90
m
40
m
50
m
RXQ5PA
Maximum
allowable
level difference
Maximum
allowable
piping length
Between the outdoor units
and the indoor units
Between the indoor units
Between the outdoor units (Multiple use)
Between the first indoor branch and the farthest indoor unit
Between the outdoor branch and the last outdoor unit
Total extension length
Refrigerant piping length
15 m or less
90 m or less
5 m or less
90 m or less
q
s
r
r
a+b+c+d+e+f+g+h+i
a+f+g+h+i
f+g+h+i
k+p
165 m or less 190 m or less
1000 m or less
90 m or less*
*
1
10 m or less 13 m or less
Actual
piping length
Equivalent
piping length
Example
Level
Difference
Example
RXQ8PA-54PA
50 m or less r
RXQ5PA
RXQ8PA-54PA
Outdoor Units
2 Available on request
If the outdoor unit is above.
If the outdoor unit is below.
If the outdoor unit is above.
If the outdoor unit is below.
40 m or less r
1. No special requirements up to 40 m. The maximum actual piping length can be 90 m, or less depending on conditions. Various conditions
and requirements have to be met to allow utilisation of 90 m piping length. Be sure to refer to the Engineering Data for details of these
conditions and requirements.
2. Level differences above 50 m are not supported by default but are available on request for RXQ8PA-54PA. (If the outdoor unit is above the
indoor unit.)
Все каталоги и инструкции здесь: http://splitoff.ru/tehn-doc.html

Table of Contents

Other manuals for Daikin VRV III

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin VRV III and is the answer not in the manual?

Daikin VRV III Specifications

General IconGeneral
TypeVRV (Variable Refrigerant Volume)
RefrigerantR410A
Energy EfficiencyHigh
ControlCentralized control systems, individual zone control
Operating Temperature Range (Cooling)-5°C to 46°C
Indoor Unit TypesCeiling Cassette, Ceiling Suspended, Wall Mounted, Floor Standing, Ducted
Power Supply380-415V, 50/60Hz, 3-Phase (depending on model)

Related product manuals