Installation ED34-862
408 FXUQ-MA
[ WIRING EXAMPLE ]
[PRECAUTIONS]
1. Use round crimp-style terminals for connecting wiring to the power supply terminal block.
If unavailable, observe the following points when wiring.
Do not connect wiring of different gauge to the same power supply terminal.
(Looseness in the connection may cause overheating.)
Use the specified electric wiring. Connect the wiring securely to the terminal. Lock the wiring down with-
out applying excessive force to the terminal. (Tightening torque: 131N·cm ±10 %)
2. Tightening torque for the terminal screws.
Use the correct screwdriver for tightening the terminal screws. If the blade of screwdriver is too small, the
head of the screw might be damaged, and the screw will not be properly tightened.
If the terminal screws are tightened too hard, screws might be damaged.
Refer to the table below for the tightening torque of the terminal screws.
3. Do not connect wiring of different gauge to the same grounding terminal. Looseness in the connection
may deteriorate protection.
4. Outside of the unit, keep the weak wiring (gas piping thermistor lead wire, transmission wiring) at least
50 mm away from strong wiring (power supply wiring, inter-unit wiring, ground wire, and other power
wiring). The equipment may malfunction if subjected to electrical (external) noise.
5. For remote controller wiring, refer to the “INSTALLATION MANUAL OF REMOTE CONTROLLER”
attached to the remote controller.
6. Never connect power supply wiring to the terminal block for remote controller wiring. A mistake of
the sort could damage the entire system.
7. Use only specified wiring and tightly connect wiring to terminals. Be careful wiring do not place external
stress on terminals. Keep wiring in neat order and so as not to obstruct other unit such as popping open
the control box lid. Make sure the lid closes tight. Incomplete connections could result in overheating, and
in worse case, electric shock or fire.
Terminal Size Tightening torque
Transmission terminal block (2P) M3.5 0.79 – 0.97N·m
Power supply and inter-unit wiring terminal block (6P) M4 1.18 – 1.44N·m
Ground terminal M4 1.44 – 1.94N·m
Electric wiring
Round crimp-style terminal
Attach insulation sleeve
Fit the power supply wiring of each unit with a switch and fuse as shown in the drawing.
COMPLETE SYSTEM EXAMPLE (3 systems)
Power supply wiring
Transmission wiring
Switch
Fuse
Power supply
Main switch
Remote controller
BEV unit
Indoor unit
BS unit
(Only for Heat
recovery
system)
Fig. 17