18.4.4 To charge refrigerant: Flow chart
For more information, see "To charge refrigerant"[4102].
Pre-charging refrigerant
Step 1
Calculate additional refrigerant charge amount: R (kg)
Refrigerant overcharge happened, recover
refrigerant to reach R=Q
Step 2+3
Close valves C, D and A
Open valve B to the liquid line
Execute pre-charging amount: Q (kg)
Disconnect the manifold from the gas line and the high pressure/low
pressure gas line
Step 4a
Close valve B
Charging is finished
Fill in the amount on the additional
refrigerant charge label
Input the additional refrigerant amount via
setting [2-14]
Go to test run
Step 4b
Close valve B
R=Q R>QR<Q
Continued on next page >>
p
<
p
>
R410AN2
C D
A B