EasyManua.ls Logo

Daikin VRV IV+ - Single Outdoor Units and Standard Multi-Outdoor-Unit Combinations >20 HP

Daikin VRV IV+
176 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18 | Piping installation
Installer and user reference guide
76
REYQ8~20+REMQ5U7Y1B
VRV IV+ heat recovery
4P561154-1A – 2020.10
If Then
The outdoor unit is positioned higher
than the indoor units
Minimum connection ratio: 80%
Size up the liquid piping (refer to "To
select the piping size"[471] for more
information)
Activate the outdoor unit setting.
Refer to the service manual for more
information.
The outdoor unit is positioned lower
than the indoor units
Minimum connection ratio varies
according to the height difference
between outdoor and indoor units:
- 40~60m: 80%
- 60~65m: 90%
- 65~80m: 100%
- 80~90m: 110%
Size up the liquid piping (refer to "To
select the piping size"[471] for more
information)
Activate the outdoor unit setting.
Refer to the service manual for more
information.
No technical cooling
18.1.6 Single outdoor units and standard multi-outdoor-unit combinations >20 HP
Connection with only VRV DX indoor units
H3
1 5
H1
H2
3 2
4
a
b b
c
d
e
e
a Outdoor unit
b VRV DX indoor unit
c Multi BS unit
d BS unit
e VRV DX indoor unit

Table of Contents

Other manuals for Daikin VRV IV+

Related product manuals