EasyManua.ls Logo

Daikin VRV IV+ - To Connect the Multi Connection Piping Kit; To Connect the Refrigerant Branching Kit

Daikin VRV IV+
176 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18 | Piping installation
Installer and user reference guide
86
REYQ8~20+REMQ5U7Y1B
VRV IV+ heat recovery
4P561154-1A – 2020.10
NOTICE
Be sure to use the supplied accessory pipes when carrying out piping work in the
field.
Be sure that the field installed piping does not touch other pipes, the bottom
panel or side panel. Especially for the bottom and side connection, be sure to
protect the piping with suitable insulation, to prevent it from coming into contact
with the casing.
Connect the stop valves to the field piping using the accessory pipes supplied with
the unit.
The connections to the branch kits are the responsibility of the installer (field
piping).
18.2.6 To connect the multi connection piping kit
NOTICE
Improper installation may lead to malfunction of the outdoor unit.
Install the joints horizontally, so that the caution label (a) attached to the joint
comes to the top.
- Do not tilt the joint more than 7.5° (see view A).
- Do not install the joint vertically (see view B).
a
a
A B
7.5°
7.5°
a Caution label
NOT allowed
Allowed
Make sure that the total length of the piping connected to the joint is absolute
straight for more than 500 mm. Only if a straight field piping of more than
120mm is connected, more than 500mm of straight section can be ensured.
>120 mm
>500 mm
18.2.7 To connect the refrigerant branching kit
For installation of the refrigerant branching kit, refer to the installation manual
delivered with the kit.
Mount the refnet joint so that it branches either horizontally or vertically.
Mount the refnet header so that it branches horizontally.

Table of Contents

Other manuals for Daikin VRV IV+

Related product manuals