19 | Electrical installation
Installer and user reference guide
115
REYQ8~20+REMQ5U7Y1B
VRV IV+ heat recovery
4P561154-1A – 2020.10
Single outdoor unit
Model Minimum circuit
ampacity
Recommended fuses
REMQ5 16.1A 20A
REYQ8 16.1A 20A
REYQ10 22.0A 25A
REYQ12 24.0A 32A
REYQ14 27.0A 32A
REYQ16 31.0A 40A
REYQ18 35.0A 40A
REYQ20 39.0A 50A
Multi outdoor units
Model Minimum circuit
ampacity
Recommended fuses
REYQ10 30.0A 40A
REYQ13 30.0A 40A
REYQ16 30.0A 40A
REYQ18 37.0A 50A
REYQ20 39.0A 50A
REYQ22 46.0A 63A
REYQ24 46.0A 63A
REYQ26 51.0A 63A
REYQ28 55.0A 63A
REYQ30 59.0A 80A
REYQ32 62.0A 80A
REYQ34 66.0A 80A
REYQ36 70.0A 80A
REYQ38 74.0A 100A
REYQ40 81.0A 100A
REYQ42 84.0A 100A
REYQ44 86.0A 100A
REYQ46 89.0A 100A
REYQ48 93.0A 125A
REYQ50 97.0A 125A
REYQ52 101.0A 125A
REYQ54 105.0A 125A
For all models:
Phase and frequency: 3N~50Hz
Voltage: 380~415V