EasyManua.ls Logo

Daikin WGZ030DW - Maintenance Schedule

Daikin WGZ030DW
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IM 1131-2 57
Maintenance Schedule
Maintenance Schedule
Table 40: Periodic Maintenance Schedule
I. Compressor
A. Performance evaluation (log & analysis) * O
B. Motor
Meg. windings
X
Ampere balance (within 10%)
X
Terminal check (tight connections, porcelain clean)
X
Motor cooling (check temperature)
X
C. Lubrication system
Oil level
OX
Oil appearance (clear color, quantity)
O
Oil change if indicated by oil analysis
X
II. Controls
A. Operating Controls
Check settings and operation
X
B. Protective Controls
Test operation of:
Alarm relay X
Pump interlocks X
High and low pressure alarms X
III. Condenser
B. Test water quality X
C. Clean condenser tubes (or as required) X
D. Eddycurrent test - X
E. Seasonal protection X
IV. Evaporator
B. Test water quality X
C. Clean evaporator tubes or plates (or as required) X
D. Eddycurrent test - (or as required) X
E. Seasonal protection X
V. Expansion Valves
A. Performance evaluation (superheat control) X
VI. Compressor - Chiller Unit
A. Performance evaluation O
B. Leak test:
Compressor fittings and terminal
X
Piping fittings
X
Vessel relief valves
X
C. Vibration Isolation Test X
D. General Appearance:
Paint
X
Insulation
X
VII. Starter(s)
A. Examine contactors (hardware and operation) X
B. Verify overload setting and trip X
C. Test electrical connections X
VIII. Optional Controls
A. Hot gas bypass (verify operation) X

Other manuals for Daikin WGZ030DW