2.0 Introduction
In smaller district heating networks ligthning can be a challenge for
the connected devices like ECL Comfort 296 / ECL 310 controllers.
If not protected, Modbus interfaces are subject for being burned in
case of lightning.
Based on several market inputs and analysis we identied a need for
information.
This has resulted in the present service guide which includes
recommendations for new installations.
The document is prepared in compliance with www.modbus.org
3.0 Conclusion
1. Each nodes in the “Modbus network” (central heating station,
repeater station or individual house) are highly recommended
to have surge protector. It must be selected as per section 6
and installed as described in section 7.
2. Phoenix “PT 1X2+F-BE” (or similar products from another manu-
facturer, as per the surge protection requirement in section 6)
must be used instead of “PT 1X2-BE” in individual house installa-
tions. Refer section 8.
3. Recommendation on Modbus reference common signal con-
nection, shield connection, termination resistor connection may
be referred in section 5, 6, 7 and 8.

Other manuals for Danfoss 087H3803

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss 087H3803 and is the answer not in the manual?

Danfoss 087H3803 Specifications

General IconGeneral
BrandDanfoss
Model087H3803
CategoryController
LanguageEnglish

Related product manuals