A275.3,exampleg
BoilerON/OFFcontrolforadirectheatingcircuit(1)andamixingcircuit(2).
*=pressurereliefvalve
Heatingcircuit2canalternativelybeafloorheatingcircuit.
SpecialsettingsfortypeA275.3,exampleg:
Navigation:
IDno.:
Recommendedsetting:
Heatingcircuit(circuit1)
Circuit1mustbeabletoreceiveaheatdemand(desiredflowtemperature)fromcircuit2:
MENU\Settings\Application:'Demandoffset'
11017
3K**
**Thisvalueisaddedtotheheatdemandvaluefromcircuit2
Heatingcircuit(circuit2)
Circuit2mustbeabletosendaheatdemand(desiredflowtemperature)tocircuit1:
MENU\Settings\Application:'SenddesiredT'
12500
ON
VI.GU.L2.02
©Danfoss|2017.09|31
OperatingGuideECLComfort210/296/310,applicationA275/A375