A375.1,examplef
Upto4xboilerON/OFFcontrolforaheatingcircuit.
*=pressurereliefvalve
Rotatingsequenceoftheboilers:Boiler1-2-3-4.Nextday:Boiler2-3-4-1.Followingday:Boiler3-4-1-2andsoon.
Burnerstepsareactivatedaccordingtoheatdemand.
Thelastburnerstepcanbedisablediftheoutdoortemperaureishigherthanasetvalue.
SpecialsettingsfortypeA375.1,examplef:
Navigation:
IDno.:
Recommendedsetting:
Heatingcircuit(circuit1)
Sequencetype(code)forcontrollingtheburners:
MENU\Settings\Boiler:'Sequencetype'
110720
Numberoftotalburnersteps:
MENU\Settings\Boiler:‘Steps'
11073
4
VI.GU.L2.02
©Danfoss|2017.09|37
OperatingGuideECLComfort210/296/310,applicationA275/A375