[39] Display Text 3 Enables an individual text string to be written, for display in the LCP or to be read via serial com-
munication.
[89] Date and Time Readout Displays the current date and time.
[1501] Running Hours View the number of running hours of the motor.
[1502] kWh Counter View the mains power consumption in kWh.
[1600] Control Word View the Control Word sent from the frequency converter via the serial communication port in hex
code.
[1601] Reference [Unit] Total reference (sum of digital/analog/preset/bus/freeze ref./catch up and slow-down) in selected
unit.
[1602] Reference [%]
[1603] Status Word Present status word
[1605] Main Actual Value [%] View the two-byte word sent with the Status word to the bus Master reporting the Main Actual Value.
[1609] Custom Readout View the user-defined readouts as defined in par.0-30
Custom Readout Unit
, par.0-31
Custom
Readout Min Value
and par.0-32
Custom Readout Max Value
.
[1610] Power [kW] Actual power consumed by the motor in kW.
[1611] Power [hp] Actual power consumed by the motor in HP.
[1612] Motor Voltage Voltage supplied to the motor.
[1613] Frequency
[1614] Motor Current Phase current of the motor measured as effective value.
[1615] Frequency [%] Motor frequency, i.e. the output frequency from the frequency converter in percent.
[1616] Torque [Nm] Present motor load as a percentage of the rated motor torque.
[1617] Speed [RPM] Motor speed reference. Actual speed will depend on slip compensation being used (compensation
set in par.1-62
Slip Compensation
). If not used, actual speed will be the value read in the display
minus motor slip.
[1618] Motor Thermal Thermal load on the motor, calculated by the ETR function. See also parameter group 1-9* Motor
Temperature.
[1622] Torque [%] Shows the actual torque produced, in percentage.
[1630] DC Link Voltage Intermediate circuit voltage in the frequency converter.
[1632] Brake Energy /s
[1633] Brake Energy /2 min
[1634] Heatsink Temp. Present heat sink temperature of the frequency converter. The cut-out limit is 95 ± 5° C; cutting
back in occurs at 70 ± 5° C.
[1635] Inverter Thermal
[1636] Inv. Nom. Current Nominal current of the frequency converter
[1637] Inv. Max. Current Maximum current of the frequency converter
[1638] SL Controller State
[1639] Control Card Temp. Temperature of the control card.
[1650] External Reference Sum of the external reference as a percentage, i.e. the sum of analog/pulse/bus.
[1652] Feedback [Unit] Reference value from programmed digital input(s).
[1653] Digi Pot Reference View the contribution of the digital potentiometer to the actual reference Feedback.
[1654] Feedback 1 [Unit] View the value of Feedback 1. See also par. 20-0*.
[1655] Feedback 2 [Unit] View the value of Feedback 2. See also par. 20-0*.
3 Parameter Description ADAP-KOOL
®
Drive Programming Guide
36
MG.11.N1.02 - VLT
®
is a registered Danfoss trademark